Flame Scanner Compact Version

KLC 1000

The KLC 1000 is a UV Flame Scanner Compact Version that has been specially developed for single burner firing systems, which generate almost no radiation in the visible light spectrum or operate with very low flame modulation. The UV tube used ensures that background radiation, e.g. from glowing brick linings or mixing equipment parts, is not detected.

The flame signal intensity can be easily recognized via an LED as a visual indicator. The KLC 1000 can be connected directly to the ionization or LDR input of the automatic burner control unit. Its dimensions, connection dimensions and pin assignment are compatible with other devices from the KLC series. All accessories are therefore identical and reduce the variety of parts in production and service.

The KLC 1000 UV flame monitor is designed in accordance with EN 298:2012-11 for automatic burner controls that check whether a flame signal is still present after a control shutdown, whereby the flame amplifier is still connected to the voltage.

  • Compact design
  • Evaluates the flicker frequency under processor control
  • Interfering extraneous light sources are blocked out
  • Signal can be evaluated on the PC via optical interface
  • Can be connected to all automatic burner controls with LDR or ionization input

The KLC 1000 is a compact UV flame detector that has been specially developed for single burner firing systems that generate almost no radiation in the visible light spectrum or operate with very low flame modulation. The UV tube used ensures that background radiation, e.g. from glowing brick linings or mixing equipment parts, is not detected.

The flame signal intensity can be easily recognized via an LED as a visual indicator. The KLC 1000 can be connected directly to the ionization or LDR input of the automatic burner control unit. Its dimensions, connection dimensions and pin assignment are compatible with other devices from the KLC series. All accessories are therefore identical and reduce the variety of parts in production and service.

The KLC 1000 flame monitor is designed in accordance with EN 298:2012-11 for automatic burner controls that check whether a flame signal is still present after a control shutdown, even though the flame amplifier is permanently energized.

The KLC 1000 should be installed tightly and in direct alignment with the flame. It must be mounted using the KLC mounting flange or a suitable holder with a 14 mm opening. The flame detector must be firmly inserted into the holder. No extraneous light should fall on the sensor.

To prevent malfunctions, the direct view of an ignition spark must be avoided. This can cause faults in the pre-ventilation phase. The maximum cable length of the connection cable must be observed. The connection cable must be routed separately from high-energy ignition and mains cables and must not be laid parallel to them over long distances. For safety reasons, there must be at least one regular switch-off every 24 hours. For the KLC 1000 version, the automatic burner control unit to be used must check the flame detector for the presence of a flame signal after the control switch-off in order to test the UV tube in accordance with EN 298. Otherwise, the KLC 11 version must be used.

Accessories

Everything you need

Do you have a question about our service portfolio, need planning support for a project or are you looking for a specialist in flame monitoring? Then please contact us.

The read-out unit UVT-COM is the interface for transmitting signals from the LEDs of KLC10, KLC1000, KLC11, KLC1001, IFX11 and IFX50 to the BST-Com software.
Heat-insulated adapter for direct installation on the firebox.
With the optionally available angle adapter, the radial alignment of the KLC 20 or KLC 21 to the flame axis is carried out using an optimally shaped mirror surface.
In addition to our standard range, we also offer customer-specific solutions for the optimum connection of flame monitors to automatic burner controls.
Various fastening devices provide a secure fit on burner parts.
The flame detector relay module converts the output signal of the KLC series flame detectors into a potential-free switching output.