Flame Scanner Compact Version

CFC 200

The CFC 200  is a complete, optical flame monitoring system for single and multi-burner systems.

  • Kompaktes Design
  • Fehlersicherer Aufbau
  • Suitable for continuous, intermittent and 72-hour operation
  • Visualization for flame relay and intensity on the device via LEDs
  • Adjustable sensitivity via control terminal
  • Approved according to international standards
  • Use at ambient temperatures* from -55 °C to +85 °C
  • Umgebungstemperaturen optional mit Lichtwellenleitereinsatz bis 300/600 °C

The flame scanner compact version 200 is a complete, optical flame monitoring device for single and multi-burner systems. Its compact design integrates the flame relay and the analog output in the device and provides the binary signal “Flame ON/OFF” and
the analog signal “0/4 to 20 mA” directly. It is suitable for continuous operation thanks to its fail-safe design and electronic self-monitoring.

Die Flammenstrahlung wird über eine Linse mit 2,7° Öffnungswinkel und den Lichtwellenleiter durch einen Halbleitersensor detektiert und elektronisch ausgewertet. Der kleine Öffnungswinkel der Linse bietet insbesondere bei Sichtrohren mit kleinen Durchmessern sowie der Fremdlichtdiskriminierung signifikante Vorteile.

Thanks to the specified ambient temperature range* of -55 °C to +85 °C, the CFC200 compact flame controller can be used for many industrial applications.

Der Lichtwellenleiter erweitert den Einsatztemperaturbereich am Brenner auf +300 °C ohne Kühlung. Lichtwellenleiterlanzen mit Kühlung erreichen eine Temperaturfestigkeit von bis zu +600 °C und sind für den Einsatz im Brenner konstruiert.

Accessories

Everything you need

Do you have a question about our service portfolio, need planning support for a project or are you looking for a specialist in flame monitoring? Then please contact us.

The CFC Ex connection housing is mounted close to the burner and enables easy installation and removal of the CFC.
The fiber optic cables are an extension of the application range of our flame monitoring devices.
For connecting flame scanner and flame detector (System 3000) with highly efficient protection
For connecting compact flame controller CFC and burner control unit with highly efficient protection.
For simulating a flame for flame sensors/compact flame monitors.
Setting the viewing axis of the flame scanner/compact flame scanner for standard, Ex enclosures and fiber optic technology.
The main effect is to reduce the internal temperature to prevent overheating.
Ball flange for aligning the flame sensor / compact flame monitor on the sight tube of the burner.
Temperature barrier and potential separation between sight tube and flame scanner/compact flame detector.
Connection element optionally with integrated pressure glass pane protects the flame monitor from pressurization from the combustion chamber.
Protects the Flame Scanner / Compact Flame Controller from pressurization from the combustion chamber. Optionally available with flushing media flange and for higher pressures.
The SKL sensor head is used to connect the BFI fiber optic cable to the sight tube of the respective application.
The SKL4DB sensor head is equipped with a metal-fused pressure glass pane, which protects the sensor optics from pressurization of the combustion chamber.
The quick-release fastener for BFI Ex enclosures enables quick and torsion-free installation of the sensors and compact flame detectors in the Ex enclosure as well as easy maintenance access without having to remove the connecting cable of the devices.